1) APPLICATION. This Section shall apply to radiant heating units installed in the Village of Whiting. No person shall install a radiant heating unit which fails to comply with the requirement of this Section.#
2) DEFINITIONS. Radiant heating unit is a room heater, or stove, or freestanding fireplace not intended for duct connections used to heat a room or rooms that use the combustion of a solid fuel such as wood or coal as a source of heat.#
3) PERMIT. No person shall install or cause to be installed a radiant heating unit without first obtaining a permit from the Building Inspector. The Building Inspector shall give each permit applicant the following information:#
a. The wood burned should be dry wood, preferably dry hardwood.#
b. The chimney flue should be checked periodically to be sure the flue is open.#
c. The chimney flue should be cleaned at least once a year.#
4) PERMIT FEE. A fee of Five ($5.00) Dollars shall be paid by the applicant for each unit installed.#
5) PLAN AND DATA APPROVAL. Plans and data for each radiant heating unit installation shall be submitted to the Building Inspector for approval before a permit may be issued. The following data is required to be submitted with each application:#
a. The manufacturer’s installation and maintenance/operations instructions.#
b. Purposed chimney flue and/or new chimney flue sizes.#
c. The number and sizes of existing vent connectors to the chimney flue.#
6) INSPECTION. No person shall operate or permit the operation of a radiant heating unit without first calling for an inspection and receiving final approval from the Building or Fire Inspector.#
7) INSTALLATION CLEARANCES. The clearance from combustibles for heating units shall be:#
a. From front of unit forty-eight (48”) inches.#
b. From top-front and sides of unit thirty-six (36”) inches.#
c. Chimney for vent connector eighteen (18”) inches.#
8) MOUNTING OF UNIT.#
a. On incombustible floors. The unit shall be mounted on a firm level base of concrete brick or other incombustible material.#
b. On combustible floors. The unit shall be mounted on a four (4”) inch thick concrete block base with circular or rectangular holes or equivalent incombustible material so arranged that the holes will parallel the smaller dimension and be covered with sheet metal of not less than No. 24 U.S. gauge. The above specified floor protection shall extend not less than eighteen (18”) inches around the perimeter of the unit.#
c. With legs on combustible floors. Units which have eighteen (18”) inches or more of open space under units may be mounted on combustible floors provided that the floor under the unit is protected with not less than one-fourth (1/4”) inch of asbestos millboard and covered with metal of not less than No. 24 U.S. gauge. The above specified floor protection shall extend not less than eighteen (18”) inches around the perimeter of the unit. If there is less than eighteen (18”) inches of open space under the base of the unit, the unit shall be mounted on two (2”) inches of concrete block, brick or other incombustible material and equally covered with sheet metal of not less than No. 24 U.S. gauge. The above specified floor protection shall not extend less than eighteen (18”) inches around the perimeter of the unit.#
9) SIZE AND TYPE OF CHIMNEY. An approved chimney shall be used for solid fuel-burning equipment. All residential buildings shall be required to have a Class “A” chimney, except as provided in Wis. Adm. Code Ind. 23.04 and 23.11. The chimney shall be sized so that the cross-sectional area of the chimney is not smaller than the cross-sectional area of the flue collar of the equipment to be connected to it. Other equipment shall not be connected to the flue serving the solid fuel-burning equipment. Masonry chimneys constructed according to the requirements of Chapter 813 of the Federal Housing Administration Minimum Property Standards FHA. No. 30 and factory-built chimneys bearing a listing by a nationally recognized testing laboratory such as Underwriters will be considered as approved.#
10) THE CHIMNEY CONNECTOR. The chimney connector shall conform to Chapter 813 of the Federal Housing administration Minimum Standards.#
11) DAMPER. The Chimney connector shall have a cast iron damper to control the draft.#
12) COMBUSTION AIR. If the Inspector, after examination of the unit, deems it necessary to add combustion air, the size of the opening shall not be less than the cross-sectional area of the blue-collar size of the unit.#
13) BLOWER. A blower where used should have adequate protection such as a screen to prevent material from being inserted into the assembly.#
14) ELECTRICAL CONNECTIONS. The electrical connections, controls, and wiring where used should conform to Village electric codes.#
15) THERMOSTAT CONTROL. The Thermostat Controls, where used, shall activate the blower motor at a temperature of one hundred (100º) degrees F. to one hundred twenty (120º) degrees F.#